Permit Number: T05BU01651
Parcel: Unknown

Address:
225 W CORONA RD

Review Status: Completed

Review Details: GRADING

Permit Number - T05BU01651
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/18/2005 DOUG WILLIAMS ENGINEERING REVIEW Denied Grading Plan:

Please provide a copy of the stamped approved Tentative Plat for reference with three sets of revised Grading and Stormwater Pollution Prevention Plans (SWPPP's) and three SWPPP texts or reports. Please completely address all comments provided below on revised Paving/Grading Plans and in a detailed response letter:

1. Provide an administrate or project address on sheet 1
2. Revise Paving and Grading General Note 31 tor reflect grading conformance to Development Standard 11-01.0.
3. Provide a project or local benchmark with a description and elevation based on NAVD 1988.
4. Add notation to Keynote 7 (sheet 4) to provide truncated domes, in accordance with ADA Accessibility Guidelines (ADAAG).
5. Provide a note specifying a right of way permit requirement adjacent to the 12" bleeder pipe callout note and detail G on sheet 3.
6. Differential Grading criteria applies to the proposed grading as presently depicted. Please refer to Development Standard 11- 01.8.1 for detailed requirements that must be met prior to grading plan approval.

SWPPP:

1. Provide the owner's certification signature and date on page 11 of the SWPPP report.
2. Include the contractor's certification signature and date if known.
3. Please include a phone number under the Contractor's Note (Sheet 1/2, lower left) for non-compliance notification/reporting purposes.

Additional comments may be necessary upon resubmittal depending on the nature and extent of revisions that occur to the plans.

If you have any questions, I can be reached at 791-5550, extension 1189 or via email at Doug.williams@tucsonaz.gov

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
07/21/2005 DAVID RIVERA ZONING REVIEW Denied 07/21/05

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning could not verify that the grading plan was in compliance with the approved tentative plat. Please submit one copy of the CDRC approved and stamped tentative plat, landscape, and NPPO plans with the next grading plan submittal.

3. Zoning will re-review the grading plan on the next submittal to insure compliance with the CDRC approved and stamped tentative plat. Additional comments may be forthcoming.

4. Per a Fedreral mandate truncated domes (early warning sysytems are required at access ramps. See Engineering comments related to the new requirement.
07/22/2005 ANDREW CONNOR NPPO REVIEW Denied Submit stamped approved tentative plat including landscape and NPP plans to continue review.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/26/2005 JMORALE1 OUT TO CUSTOMER Completed
07/26/2005 ANGIE SHOFFSTALL REJECT SHELF Completed