Review Details: WALLS
Permit Number - T05BU01583
Review Name: WALLS
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 08/24/2005 | MICHAEL ST. PAUL | ZONING | REVIEW | Approved | |
| 08/24/2005 | ANY | ENGINEERING | REVIEW | Approved | The design of the walls must address: 1. The soils must be able to support the walls, retained soil and retained water even when subject to repeated inundation. 2. All walls must be designed to retain water. 3. Wall elevations must match the approved grading plan. |
| 08/24/2005 | MICHAEL ST. PAUL | NPPO | REVIEW | Approved | |
| 08/24/2005 | CHRISTY FOREMAN | BUILDING-RESIDENTIAL | REVIEW | Needs Review | 1) WALLS NEED TO RETAIN SOIL PLUS BE DESIGNED FOR INUNDATION WITH WATER. 2) ALL WALLS NEED TO BE DESIGNED TO RETAIN WATER. 3) ELEVATIONS OF WALL NEED TO BE PER APPROVED GRADING PLAN. |
| 08/24/2005 | ANY | ENGINEERING | REVIEW | Approved | Previous comments adequately addressed Loren Makus 8-26-05 |