Permit Number: T05BU01503
Parcel: 126211530

Review Status: Completed

Review Details: GRADING

Permit Number - T05BU01503
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/30/2005 JOSE ORTIZ ENGINEERING REVIEW Denied To:Frank Petridis DATE: June 30, 2005
168 S. Randolph Way FROM: Jose Ortiz
Tucson, Arizona 85716 Engineering Division


SUBJECT: Privada Colonia Solana Lots
Grading Plan T05BU01503 (First Review)
T14S, R14E, Section 16

RESUBMITTAL REQUIRED: Grading Plan, approved Tentative Plat, and Drainage Report

The Grading Plan (GP) and Drainage Report (DR) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Please include a response letter to the comments along with the corrected copies of the GP.
2. Lettering appears too small. All lettering and dimensions shall be equivalent of twelve (.12") point or greater size. The purpose of this requirement is to assure that all lettering is legible when reviewed and will maintain that legibility when reproduced and photographically reduced for record keeping purposes.
3. Add note: "Depress all landscaped areas a maximum of 6" for water harvesting".
4. Add the basin(s) maintenance responsibility note per S.M.D.D.F.M. 2.3.1.6 C 1 and 2 to the GP.
5. List subdivision number. Clarify whether the number is S98-060 or S98-068.
6. Show all symbols in the legend. Legend may need to be updated to show additional items such as setbacks and easement line work.
7. Cloud in revisions and provide dates.
8. Show limits of grading.
9. In the street cross section provide transverse and longitudinal slopes.
10. Please show the proposed roof drainage patterns.
11. If applicable provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. 100% of the 10-year flow must be conveyed under the sidewalks. If the location(s) of the roof scuppers have not yet been decided, add a general note indicating sidewalk scuppers (per COT/SD) will be used when the roof scuppers locations have been designed.
12. Curb and Gutter elevation include drainage flow with percent slope.
13. Show details of all surface materials.
14. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
15. Drainage patterns with percent slopes (Show patterns within the first 100 feet from the property line).
16. Flow arrows, grades and flow rates within and adjacent to site to show drainage scheme.
17. Call out peak discharges entering and exiting the site.
18. Detail of wall openings (size and distance).
19. Cross section across property line showing clear acceptance of off-site flow.
20. Provide adequate spot elevations and/or contour lines existing and proposed. Existing (dashed) and proposed (solid) contours and/or appropriate number of spot elevations.
21. Prevent nuisance ponding off-site due to development.
22. Finish floor elevations and pad elevations. FP should read FFE.
23. If applicable provide FFE for houses within 100 feet from outside perimeter of site.
24. Call out contour interval.
25. Provide existing contours around site to at least 25' from property line.
26. Show grade breaks.
27. Proposed FFE's should not exceed 2 feet from existing house adjacent to site.
28. Call out slopes on section B-B.
29. Flow arrows, grades and flow rates within and adjacent to site to show drainage scheme.
30. (Call out flow peak discharges entering and exiting site).
31. Detention/Retention Basins:
Must match drainage report
Inlet/outlet structural details (weir design); provide dimension of weir openings
Cross sections and dimension; dimension widths of all drainage sections
Dimension basin, provide spot elevations/flow arrows (i.e. drainage easement on lots 4-7)
Water surface elevations onto cross sections
Peak Discharge at basin's outlet!

32. Per recently revised city policies the sidewalk along Broadway shall be 6' wide and 5' wide on Via Palos Verdes.
33. It appears that there is a bust in the grades on Lot 6.

Drainage report:
1. Please include a response letter to the comments along with the corrected copies of the DR.
2. The content and format of the Hydrology report should follow S.M.D.D.F.M., chap. II, 2.1.3.
3. Show the project address on the cover of the Hydrology report.
4. Add the basin(s) maintenance responsibility note and checklist per S.M.D.D.F.M. 2.3.1.6 C 1 and 2.


If you have any questions, I can be reached at 791-5550 x1191 or at Jose.Ortiz@tucsonaz.gov
Jose E. Ortiz
Civil Engineer
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
07/11/2005 ANDREW CONNOR NPPO REVIEW Denied Submit stamped approved landscape and NPP plans included in tentative plat Case # S98-068 to continue review.
07/16/2005 DAVID RIVERA ZONING REVIEW Denied 07/16/05

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

2. Zoning will re-review the grading plan on the next submittal to insure compliance with the CDRC approved and stamped tentative plat. Additional comments may be forthcoming.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/19/2005 KMEDINA1 OUT TO CUSTOMER Completed