Permit Number: T05BU01366
Parcel: 13614011E

Address:
8200 E STELLA RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T05BU01366
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/28/2005 ANDREW CONNOR NPPO REVIEW Denied 1. Plans shall be of sufficient clarity to indicate the nature and extent of the work proposed and show in detail that they will conform to the provisions of this code and all relevant laws, ordinances, rules and regulations per DS 11-01.4.1.C. Clearly indicate on grading plan the limits of disturbance and natural areas identical to approved NPP included in approved tentative plat.

2. Add note to grading plan: All plants designated to be preserved-in-place shall be retained at their existing grade during and after construction. Preservation fencing per DS 2-06. Figure 1 is required to be installed beyond the "drip-line" of the vegetation by one-half (½) the distance of the "drip-line" radius. DS 2-15.6.A

3. Note on grading plan: Prior to any site disturbance a pre-grading inspection is required. Inspections may be scheduled by calling the IVR system at (520) 740-6970, inspection #09015 or by calling the Landscape Field Representative directly at 791-5640 Ext. 1140.
10/07/2005 LAITH ALSHAMI ENGINEERING REVIEW Denied Laith Alshami, Engineering and Floodplain Review, 10/10/2005


SUBJECT: Lakeside Ridge
Grading Plan T05BU01366 (First Review)
T14S, R15E, Section 28

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report and CLOMR and/or LOMR.

The Grading Plan (GP) and Stormwater Pollution Prevention Plan cannot be approved as submitted. We offer the following comments:

1. Include response letter to the comments along with the corrected copies of the GP.
2. Include the redlined copy of the Grading plan.
3. Complete the Bk. and Pg. on the title of the cover sheet.
4. The Grading Plan can not be approved without the flood plain use permit, which is required for any work done within the 100-year flood plain limits.
5. Show details of all surface materials, including thickness dimensions.
6. Call out all slopes and stabilization material (concrete, riprap, Gabion or vegetation) as recommended by the Geotechnical Report. Provide a copy of the Geotechnical Report.
7. Verify compliance with the 404-Permit requirements.
8. Stormwater pollution prevention plan is acceptable; however, it can not be approved until the Grading Plan is approved.
10/20/2005 DAVID RIVERA ZONING REVIEW Denied 10/19/05

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering, and Landscape Review Sections and until all zoning comments or concerns have been addressed.

Final Status

Task End Date Reviewer's Name Type of Review Description
10/25/2005 DELMA ROBEY OUT TO CUSTOMER Completed
10/25/2005 DELMA ROBEY REJECT SHELF Completed