Permit Number: T05BU01319
Parcel: 10120040D

Review Status: Completed

Review Details: GRADING

Permit Number - T05BU01319
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/03/2005 ELIZABETH EBERBACH ENGINEERING REVIEW Approved DATE: June 6, 2005
TO: Pat Lowry, WRG Design
SUBJECT: 3030 W EL CAMINO DEL CERRO Grading Plan Review
LOCATION: T13S R13E Section 17
REVIEWER: Elizabeth Eberbach
ACTIVITY NUMBER: T05BU01319

SUMMARY: Engineering Division of Development Services Department has received the Site/Grading/SWPPP submittal. The Grading Plan was reviewed and Engineering recommends conditional approval. The following conditions apply.

CONDITIONS GRADING PERMIT:
1) A REVISED SWPPP WILL BE REQUIRED TO BE SUBMITTED FOR REVIEW PRIOR TO GRADING PRE-CONSTRUCTION MEETING. THE SWPPP SHALL INCLUDE A COMPLETED CONSTRUCTION CHECKLIST THAT CAN BE FOUND AT: http://www.azdeq.gov/environ/water/permits/download/cswppp.pdf . THE STORMWATER POLLUTION PREVENTION PLAN (SWPPP) SHALL INCLUDE THE AZPDES CONSTRUCTION GENERAL PERMIT (AZG2003-001) http://www.azdeq.gov/environ/water/permits/download/constgp.pdf . THE STORMWATER POLLUTION PREVENTION PLAN (SWPPP) SHALL BE SUBSEQUENTLY UPDATED AS NEEDED AND KEPT ON SITE DURING GRADING. A COPY OF THE SWPPP WITH THE NOI SHALL BE AVAILABLE AT THE GRADING CONSTRUCTION SITE.
2) CALL FOR SWPPP INSPECTION AND PRE-CONSTRUCTION MEETINGS. FOR A DSD ENGINEERING INSPECTIONS, CALL IVR (740-6970), OR SCHEDULE WITH A CUSTOMER SERVICE REPRESENTATIVE AT THE DEVELOPMENT SERVICES DEPARTMENT, OR SCHEDULE INSPECTIONS ONLINE AT: HTTP://WWW.CI.TUCSON.AZ.US/DSD/ONLINE_SERVICES/ONLINE_PERMITS/ONLINE_PERMITS.HTML OR CONTACT DSD ENGINEERING AT 791-5550 EXTENSION 2101.
3) ALL WORK SHALL CONFORM TO THE APPROVED GRADING AND DRAINAGE PLAN SHEET C2 FOR JACK-IN-THE-BOX, INC, ACTIVITY NUMBER T05BU01319, BY WRG DESIGN INC. (SEALED 5/25/05), AND ANY ASSOCIATED GEOTECHNICAL ENGINEERING AND DRAINAGE REPORTS, WHICH ARE MADE PART OF THIS PERMIT. SEE GRADING PLAN SHEET C2 FOR DRAINAGE AND GRADING INFORMATION. SHEETS C1, SD1.0, SD1.1, AND SD2.0 ARE SITE PLAN REFERENCE ONLY.
4) GRADING (INCLUDING ECAVATION, FILL, AND PAVEMENT THICHNESS) SHALL CONFORM TO THE GEOTECHNICAL RECOMMENDATIONS FROM SPEEDIE AND ASSOC., DATED 10-31-03, AND ANY ASSOCIATED ADDENDA.
5) ASSOCIATED ACTIVITY NUMBERS: T05CM01648, T04OT01081, AND T05OT01342.
6) A RESEED BOND IN THE AMOUNT OF $4,791.60 IS REQUIRED TO BE SUBMITTED AT TIME OF PERMIT ISSUANCE AND IS BASED ON THE TOTAL DISTURBANCE AREA IN SQUARE FEET AT $0.05 PER SQUAREFOOT.
7) THE 8-INCH BLEED PIPE SHALL HAVE EROSION PROTECTION PLACED AT OUTLET.
8) ANY REVISION TO THE GRADING PLAN MAY REQUIRE A RE-SUBMITTAL OF THE REVISED GRADING PLAN FOR REVIEW. CONTACT DSD ENGINEERING AT 791-5550 TO DISCUSS ANY CHANGES IN GRADING DESIGN.
9) IF GRADING CONSTRUCTION IS EXPECTED TO LAST LONGER THAN THE EXPIRATION DATE ON THE GRADING PERMIT, CONTACT DSD TO RENEW OR EXTEND THE GRADING PERMIT. IF THE FINAL GRADING INSPECTION HAS NOT BEEN COMPLETED BEFORE THE GRADING PERMIT EXPIRES, AND THE GRADING PERMIT HAS NOT BEEN RENEWED, ADDITIONAL FEES AND REVIEWS MAY BE REQUIRED.
10) AS-BUILTS REQUIRED, WITH COMPLETION DOCUMENTATION (INCLUDING THE SUBSTANTIAL COMPLETION OF BASIN IN CONFORMANCE TO THE DRAINAGE REPORT AND PLANS) FROM PROJECT ENGINEER AT TIME OF FINAL GRADING INSPECTION.
11) CONTACT PERMITS AND CODES (791-5100) FOR ANY RIGHT-OF-WAY PERMIT AND REQUIREMENTS.

For further clarification, call me at 791-5550, extension 2204.
Elizabeth Eberbach, PE
Civil Engineer
Engineering Division
Development Services Department
06/17/2005 DAVID RIVERA ZONING REVIEW Approved
06/20/2005 ANDREW CONNOR NPPO REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
06/23/2005 ANGIE SHOFFSTALL APPROVAL SHELF Completed
06/23/2005 CINDY AGUILAR OUT TO CUSTOMER Completed