Permit Number: T05BU01308
Parcel: 116094100

Address:
2975 W SALVIA DR

Review Status: Completed

Review Details: GRADING

Permit Number - T05BU01308
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/17/2005 ANDREW CONNOR NPPO REVIEW Approv-Cond
06/21/2005 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: Montage Vista Lot 62
REVIEWER: Doug Williams
DATE: 21 June 2005
ACTIVITY NUMBERS: T05BU01308

SUMMARY: Engineering Division has reviewed the subject grading plan. Approval is not recommended at this time. Please address the following comments in a response letter and a revised grading plan:

1. Please refer to Section 11.8.1 of the City of Tucson's Development Standards for placement of fill in excess of 2 feet above existing grade in the outer 100 feet of the developing site. The proposed grading for this lot indicates placement of fill in excess of 2' above existing grade for the upper pad, and conformance to this standard must be demonstrated prior to grading permit approval. Please assure all necessary documentation, written permission and any mitigation plan information is provided with a resubmittal.
2. Revise the sheet number identified in call-outs A, B and C to refer the reader to sheet G2.
3. Provide a note stating that a separate retaining wall permits will be required, wherever depicted or noted on the plan.
4. Please provide a copy of a standard soils/geotechnical recommendations, specifically addressing all setback, grading, slope, interceptor swale and terracing recommendations, at a minimum.

Resubmittal shall include 3 copies of a revised grading plan addressing the comments provided above, and a copy of the geotechnical report/recommendations.

If you have any questions, I can be reached at 791-5550, extension 1189 or Doug.willias@tucsonaz.gov

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
06/30/2005 DAVID RIVERA ZONING REVIEW Denied 06/30/05

Development Services Department
Zoning Review Section

David Rivera
Principal Planner

Comments:

1. The grading plan has been reviewed by Zoning Review Section but cannot approve the plan until it has been approved by the Engineering.

Final Status

Task End Date Reviewer's Name Type of Review Description
07/16/2005 GBONILL1 OUT TO CUSTOMER Completed
07/05/2005 ANGIE SHOFFSTALL REJECT SHELF Completed