Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T05BU01178
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/31/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Denied | Grading Plan 1. As per FIRM Panel 2232K the water surface elevation is 2495.50 (NGVD29) for the proposed structure, therefore the structure's finished floor elevation will be set one foot above the WSE which is 2496.50 Justify the proposed FFE of 2500.40 2. The proposed FFE is 2500.40, which exceeds by 3.90 feet above the calculated elevation. The proposed amount of fill exceeds the two-foot grading differential rule, which is not acceptable for areas adjacent to R2 Zones. DS 11-01.8.1.A Correct and revise. 3. Indicate existing grades and grade breaks. 4. Demonstrate the 5-foot sidewalk transition from curb cut to being flushed with asphalt. Indicate a dimensioned cross section detail of PAAL 5. The geotechnical report will adhere to the grading and floodplain ordinance for site preparation and fill quantities. 6. Grading work is not to encroach the adjacent properties. All grading work is to remain on proposed site. |
| 06/03/2005 | DAN CASTRO | ZONING | REVIEW | Denied | Zoning Review may not approve the grading plan prior to Engineering and Landscape approval. |
| 06/07/2005 | ANDREW CONNOR | NPPO | REVIEW | Denied | Site plan approval in necessary to continue review. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 06/08/2005 | DHERRON1 | OUT TO CUSTOMER | Completed |
| 06/08/2005 | DHERRON1 | REJECT SHELF | Completed |