05/31/2005 BLANCA ESPINO ENGINEERING REVIEW Denied Grading Plan
1. As per FIRM Panel 2232K the water surface elevation is 2495.50 (NGVD29) for the proposed structure, therefore the structure's finished floor elevation will be set one foot above the WSE which is 2496.50 Justify the proposed FFE of 2500.40

2. The proposed FFE is 2500.40, which exceeds by 3.90 feet above the calculated elevation. The proposed amount of fill exceeds the two-foot grading differential rule, which is not acceptable for areas adjacent to R2 Zones. DS 11-01.8.1.A Correct and revise.

3. Indicate existing grades and grade breaks.

4. Demonstrate the 5-foot sidewalk transition from curb cut to being flushed with asphalt. Indicate a dimensioned cross section detail of PAAL

5. The geotechnical report will adhere to the grading and floodplain ordinance for site preparation and fill quantities.

6. Grading work is not to encroach the adjacent properties. All grading work is to remain on proposed site.
06/03/2005 DAN CASTRO ZONING REVIEW Denied Zoning Review may not approve the grading plan prior to Engineering and Landscape approval.
06/07/2005 ANDREW CONNOR NPPO REVIEW Denied Site plan approval in necessary to continue review.