Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T05BU01030
Parcel: 136284320

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05BU01030
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/17/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 8/17/05
ACTIVITY NUMBER: T05BU01030
PROJECT NAME: Retaining wall
PROJECT ADDRESS: 7711 E. Irvington Rd.
ARCHITECT / ENGINEER: Bill Richardson
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) Bearing depth of existing and new footing.
2) Clarify vertical reinforcement of screen wall pg 4 structural calculations it appears #4 rebar was used to justify wall above height of 3.33 ft.
3) Clarify 4" screen wall. Calculations use 10" thick & 12" width see pg 6 of calculations.
4) Site plan must be stamped and signed. Provide dimensions for location of pilasters. Provide Grades / elevations. Provide percentage of slope for drain tile.
5) Provide detailing for drain tile, see section 1807.4.2 of IBC 2003.
6) Drawing will need to be approved by engineering and zoning again since changes were made to the drawings.
08/18/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: John Long DATE: August 18, 2005
Owner
7711 E Irvington Rd. Tucson, Arizona 85730


SUBJECT: 7711 E Irvington Road
Site plan/Wall permit T05BU01030 (First Review)
T14S, R15E, Section 32

RESUBMITTAL REQUIRED: Site Plan and Wall permit.

The Site Plan (SP) and cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Please provide correct North arrow and scale per D.S. 2-02.2.1.
3. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
4. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
5. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
6. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
7. Provide drainage blocks on the North and South walls to ensure existing drainage patterns remain the same.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/7711 E Irvington Rd site/wall
08/19/2005 PATRICIA GEHLEN ZONING REVIEW Passed approved by P Gehlen 4/29/05

Final Status

Task End Date Reviewer's Name Type of Review Description
08/24/2005 BETH GRANT OUT TO CUSTOMER Completed
08/24/2005 BETH GRANT REJECT SHELF Completed