Permit Number: T05BU01030
Parcel: 136284320

Review Status: Completed

Review Details: OTHER

Permit Number - T05BU01030
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/01/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied 1) Clarify reinforcement of existing retaining & screen wall. Provide details for wall that was built without a permit in addition to changes that are being made to justify per the IBC 2003.
2) Clarify / justify statement retaining wall takes care of itself.
3) Detail / clarify horizontal bond beam at top of wall / ties to existing wall.
3) Clarify weep holes.
4) Clarify location of wall on site plan. Clarify grades on site plan for verification which side of wall is retaining fill.
5) Clarify that all work can be done on the this property. This permit is for this property only. Will access on adjacent properties be required to complete additional work.
6) Clarify on site plan location of new CMU column and footings.
7) Engineer needs to stamp site plan.

Final Status

Task End Date Reviewer's Name Type of Review Description
06/21/2005 KMEDINA1 OUT TO CUSTOMER Completed