04/04/2006 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 04/05/06
ACTIVITY NUMBER: T05BU01030
PROJECT NAME: Retaining wall
PROJECT ADDRESS: 7711 E. Irvington Rd.
ARCHITECT / ENGINEER: Bill Richardson
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1)Provide detailing for drain tile. Backfill need to be a free draining soil to allow drainage to drain pipe. Drain pipe shall be covered with a filter membrane and granular material of aize to avoid plugging the weep hole.
2) Construction sequence and section detail need to note removal of top course and install 2-#4 for bond beam.
3) Construction sequence and section detail need to note epoxy #4 rebar into each course of existing pilaster.
04/13/2006 PAUL MACHADO ENGINEERING REVIEW Approved