Permit Number: T05BU01030
Parcel: 136284320

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T05BU01030
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/28/2005 CHRISTY FOREMAN BUILDING-COMMERCIAL REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES
STRUCTURAL REVIEW COMMENTS

DATE: 11/29/05
ACTIVITY NUMBER: T05BU01030
PROJECT NAME: Retaining wall
PROJECT ADDRESS: 7711 E. Irvington Rd.
ARCHITECT / ENGINEER: Bill Richardson
PROJECT REVIEWER: Christy Foreman



TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1108 OR EMAIL AT CFOREMA1@CI.TUCSON.AZ.US IF YOU CARE TO DISCUSS.

1) All drawings / details need to be submitted on 24" x36" sht with text size a minimum of 10 pt. This is neccessary for field and micro-filming purposes.
2) Provide detailing for drain tile, see section 1807.4.2 of IBC 2003 which pertains to all foundations, see 1801.1 scope.
12/05/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: John Long DATE: December 5, 2005
Owner
7711 E Irvington Rd.
Tucson, Arizona 85730

SUBJECT: 7711 E Irvington Road
Site plan/Wall permit T05BU01030 (Second Review)
T14S, R15E, Section 32

RESUBMITTAL REQUIRED: Site Plan and Wall permit.

The Site Plan (SP) and cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Assuming a new plot plan was generated, a copy of new Site Plan was not included in this submittal nor were the comments from the last submittal corrected with this submittal. Include the corrected Site Plan (or new) with the next submittal.
3. Please provide correct North arrow and scale per D.S. 2-02.2.1.
4. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
5. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
6. Please show dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way per D.S. 2-02.2.1.19.
7. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
8. Provide drainage blocks on the North and South walls to ensure existing drainage patterns remain the same.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/7711 E Irvington Rd site/wall 2

Final Status

Task End Date Reviewer's Name Type of Review Description
12/07/2005 GBONILL1 OUT TO CUSTOMER Completed
12/07/2005 SUE REEVES REJECT SHELF Completed