Review Details: TANKS

Permit Number - T05BU00947
Review Name: TANKS
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/21/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Denied TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

1. Minimum font size is 1/8". This applies to the Electrical Equipment Elevation Sheet E1.
2. Need to verify that Lockable Start-Stop Pushbuttons as motor disconnects are Listed Self-Protected Combination Controllers per NEC 430.109 (A) (5). Keynote 9 Sheet E2.
3. Indicate what happened to the loads on removed Panel E.
4. Plot location of Panels L1 and L2 on plans.
5. The bond in Conduits 6 & 7 Sheet E3 needs to be sized for the derived conductors in Conduit 7 per NEC Table 250.66 footnote a. (2) (750) = 1500 MCM so the bond shall be 3/0.
6. Specify the conduit type intended for the classified location.
7. Main Bonding Jumper Keynote 3a Sheet E3 shall be 4/0, not 3/0. (3) (500) (0.125) = 187.5 MCM. Reference NEC 250.28 (D), and Table 8 in Chapter 9.
8. Would like cut sheets of the controller equipment at the MCC, the Lockable Pushbutton Motor Control in the field, the new motors (as available) emailed to the above address or faxed to 520.879.8010.