Permit Number: T05BU00939
Parcel: 10711197A

Review Status: Completed

Review Details: GRADING

Permit Number - T05BU00939
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/29/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: May 6, 2005
ACTIVITY NUMBER: T05BU00939
PROJECT NAME: Estrella Homes
PROJECT ADDRESS: 3045 North Estrella Ave.
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the grading plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: GRADING PLAN

1. Grading plan approval is contingent on site plan approved.

2. Show roof drainage (flow arrows). DS 2-02.2.1.A.16.

3. Show the depth of the water harvesting areas in the landscape border. Either by a general note or label on the plan.

4. It appears there might be a differential grading issue with the proposed structures. Proposed fills in excess of two feet above existing grade at any location in the outer one hundred feet of the developing site adjacent to residentially zoned property require the procedure outlined in Development Standard 11-01.8. This process must be complete prior to Grading Plan approval. Indicate what the use is for the adjacent properties. In effort to determine if there is a differential grading issue include pad grades for each structure.

5. Indicate the grading limits (limits of disturbance) on the grading plan. Include the line weight used in the legend and label accordingly.

6. Show the location of any buildings or structures within 15' of the proposed grading. DS 11-01.4.F.1.c.

7. Indicate the use of fabric filter underneath all proposed rock rip rap.
05/09/2005 PETER MCLAUGHLIN ZONING REVIEW Denied Site plan approval required.
05/17/2005 ANDREW CONNOR NPPO REVIEW Denied Site plan approval is necessary to continue review.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/19/2005 GBONILL1 OUT TO CUSTOMER Completed
05/19/2005 SUE REEVES REJECT SHELF Completed