Permit Number: T05BU00904
Parcel: 140260440

Review Status: Completed

Review Details: COMMERCIAL TI

Permit Number - T05BU00904
Review Name: COMMERCIAL TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/19/2005 JIM EGAN FIRE REVIEW Approv-Cond Prior to final inspection information shall be provided to verify that existing fire sprinkler system design is adequate to protect rack storage of commodity to height indicated.
05/17/2005 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Passed TRANSMIT ORIGINAL DRAWINGS WITH NEXT SUBMITTAL.

PLEASE CALL AT 791-5550 X1106 OR EMAIL AT Linda.Buczynski@tucsonaz.gov
IF YOU CARE TO DISCUSS.

Sheet Index on Sheet A1 indicates that there are Electrical Sheets E1-E5 in this project. Include such sheets with next submittal. Also include the Architectural, Plumbing, and Mechanical Sheets.

5/17/05 Verified per telephone converstion with Sam Santana (488.7703) that Site Plan is documented to apply to structural racks only.
05/19/2005 ANY BUILDING-COMMERCIAL REVIEW Denied .. T05BU00904 .. 6050 S. COUNTRY CLUB ROAD .. DGL .. 1ST REVIEW .. 5/19/05 ..

S1. Provide Site Plan showing entire site with property lines and all buildings on site shown, designate location of the work.
S2. Provide Complete Architectural Floor Plan of the building in which the work is to be done (showing all rooms and their uses, doors, windows, and other architectural items located to scale), designate the location of the work by dimension from two adjacent walls of existing construction and dimension the work to locate within the building.
S3. Provide callouts on floor plan for each pallet rack section to be installed under this permit.
S4. Show depth and strength of existing floor slab on drawings and clarify compliance with plate and anchor bolt analysis in structural calculations.
S5. Clarify on drawings and in structural calculations conformance with 2003 International Building Code, as currently adopted by the City of Tucson.
S6. Specify anchor bolt to be used in structural calculations and on drawings.
S7. Special Inspection required for anchor bolts in concrete.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.

Final Status

Task End Date Reviewer's Name Type of Review Description
05/23/2005 JMORALE1 OUT TO CUSTOMER Completed
05/23/2005 ANGIE SHOFFSTALL REJECT SHELF Completed