Review Details: GRADING

Permit Number - T05BU00502
Review Name: GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/11/2005 BLANCA ESPINO ENGINEERING REVIEW Denied Grading
1. Demonstrate drainage flow along the six-inch vertical curb between parking lots.

2. Indicate grade breaks.

3. Keynote #15 on Sheet 2 of 2 indicates a two-foot curb opening. Demonstrate drainage flow for southeast area to prevent ponding.

4. Discharge flows are to remain in historic location, style and quantity. It appears that the natural state of flow has been redirected according to the contours. Justify the change.

5. Demonstrate percentage slope from parking spaces to PAAL area.

6. Delineate grading limits.
03/21/2005 TACHONG1 ZONING REVIEW Needs Review
03/21/2005 TACHONG1 NPPO REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
03/21/2005 TAMI ACHONG OUT TO CUSTOMER Completed