Permit Review Detail
Review Status: Completed
Review Details: GRADING
Permit Number - T05BU00502
Review Name: GRADING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 03/11/2005 | BLANCA ESPINO | ENGINEERING | REVIEW | Denied | Grading 1. Demonstrate drainage flow along the six-inch vertical curb between parking lots. 2. Indicate grade breaks. 3. Keynote #15 on Sheet 2 of 2 indicates a two-foot curb opening. Demonstrate drainage flow for southeast area to prevent ponding. 4. Discharge flows are to remain in historic location, style and quantity. It appears that the natural state of flow has been redirected according to the contours. Justify the change. 5. Demonstrate percentage slope from parking spaces to PAAL area. 6. Delineate grading limits. |
| 03/21/2005 | TACHONG1 | ZONING | REVIEW | Needs Review | |
| 03/21/2005 | TACHONG1 | NPPO | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/21/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |