Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T05BU00480
Parcel: 141090210

Address:
7855 S WILMOT RD

Review Status: Completed

Review Details: RESUBMITTAL - GRADING

Permit Number - T05BU00480
Review Name: RESUBMITTAL - GRADING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/09/2005 ANDREW CONNOR NPPO REVIEW Approv-Cond
08/16/2005 DAN CASTRO ZONING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
08/19/2005 SUE REEVES OUT TO CUSTOMER Completed