Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: OTHER
Permit Number - T05BU00359
Review Name: OTHER
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
03/17/2005 | DOUG LAAKSO | BUILDING-COMMERCIAL | REVIEW | Denied | .. T05BU00358 .. 827 E 17TH ST #1 .. FIRE WALL AT PROPERTY LINE FOR LOT SPLIT .. .. T05BU00359 .. 827 E 17TH ST #2 .. FIRE WALL AT PROPERTY LINE FOR LOT SPLIT .. .. DGL .. 3/22/05 .. S1. A building permit is required for : 1. Metal building (cold storage) 644 s.f. 2. Metal building 897 s.f. 3. Metal building 536 s.f., if these buildings are to remain , a demolition permit is required if these buildings are to be removed, prior to the issuance of this building permit . S2. Provide construction details and fire listings for infill, on the drawings, for Fire Wall openings including : 1. Two - door openings 2. Two - conveyor openings 3. Two- window openings at boiler room S3. Indicate, on the drawings, the occupancy/ies and type/s of construction of buildings on each side of property lines. S4. Clearly show the extent of and fire-rating of the property line /Fire Wall, this wall is required to extend through the building on each side of the 'new' property line to the face of the exterior walls. Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111. |
03/24/2005 | BOB SUBA | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
03/28/2005 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide information to show how the mechanical equipment, controls, piping, and ductwork are related to the 3-hour wall. Show how any penetrations of the wall are protected. |
03/28/2005 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Provide information to show how the water supply and waste piping systems are related to the 3-hour wall. |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
03/30/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
03/30/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |