Permit Number: T05BU00359
Parcel: 124150080

Address:
827 E 17TH ST 02

Review Status: Completed

Review Details: OTHER

Permit Number - T05BU00359
Review Name: OTHER
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/17/2005 DOUG LAAKSO BUILDING-COMMERCIAL REVIEW Denied .. T05BU00358 .. 827 E 17TH ST #1 .. FIRE WALL AT PROPERTY LINE FOR LOT SPLIT ..
.. T05BU00359 .. 827 E 17TH ST #2 .. FIRE WALL AT PROPERTY LINE FOR LOT SPLIT ..
.. DGL .. 3/22/05 ..

S1. A building permit is required for :
1. Metal building (cold storage) 644 s.f.
2. Metal building 897 s.f.
3. Metal building 536 s.f.,
if these buildings are to remain , a demolition permit is required if these buildings are to be removed,
prior to the issuance of this building permit .
S2. Provide construction details and fire listings for infill, on the drawings, for Fire Wall openings including :
1. Two - door openings
2. Two - conveyor openings
3. Two- window openings at boiler room
S3. Indicate, on the drawings, the occupancy/ies and type/s of construction of buildings on each side of property lines.
S4. Clearly show the extent of and fire-rating of the property line /Fire Wall, this wall is required to extend through the building on each side of the 'new' property line to the face of the exterior walls.

Questions? Call Douglas Laakso Structural Plans Examiner for the City of Tucson Development Services Department at (520) 791-5550 x1111.
03/24/2005 BOB SUBA ELECTRICAL-COMMERCIAL REVIEW Passed
03/28/2005 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide information to show how the mechanical equipment, controls, piping, and ductwork are related to the 3-hour wall. Show how any penetrations of the wall are protected.
03/28/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied Provide information to show how the water supply and waste piping systems are related to the 3-hour wall.

Final Status

Task End Date Reviewer's Name Type of Review Description
03/30/2005 TAMI ACHONG OUT TO CUSTOMER Completed
03/30/2005 ANGIE SHOFFSTALL REJECT SHELF Completed