Review Details: COMMERCIAL NEW
Permit Number - T05BU00308
Review Name: COMMERCIAL NEW
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/14/2005 | JIM EGAN | FIRE | REVIEW | Approved | |
| 02/17/2005 | SREEVES1 | PLUMBING-COMMERCIAL | REVIEW | Passed | |
| 02/17/2005 | SREEVES1 | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 02/17/2005 | SREEVES1 | WWM | REVIEW | Passed | |
| 02/17/2005 | SREEVES1 | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 02/17/2005 | SREEVES1 | WATER | REVIEW | Passed | |
| 03/14/2005 | RAUL PALMA | BUILDING-COMMERCIAL | REVIEW | Denied | City of Tucson, Development Services BUILDING AND STRUCTURAL COMMENTS 1) The soils pressure is limited to 1500 psf without a soils report. The general notes and the calculations specify 2000 psf. Either change the 2000 psf to 1500 psf. or provide a soils report. Also revise your ftg. design to reflect the change. 2) All calc sheets shall be presented with a 10 point font. Some of the calc`s sheets show a smaller font. 3) The structures dimensions shown on the site plan are different from those shown On the structural plan. Also, the site plan and structural plan are signed by different engineers. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 03/25/2005 | TAMI ACHONG | OUT TO CUSTOMER | Completed |
| 03/25/2005 | ANGIE SHOFFSTALL | REJECT SHELF | Completed |