Permit Number: T05BU00221
Parcel: 10509018C

Address:
4611 N 1ST AV

Review Status: Completed

Review Details: RESUBMITTAL - GRADING ALL

Permit Number - T05BU00221
Review Name: RESUBMITTAL - GRADING ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2005 LOREN MAKUS ENGINEERING REVIEW Approved DATE: May 9, 2005
TO: Geoff Harris, MMLA PSOMAS
SUBJECT: Miramonte at the River, Grading Plan Review
REVIEWER: Loren Makus
ACTIVITY NUMBER: T05BU00634

SUMMARY: The Grading Plan was reviewed by Development Services Department Engineering Division. The Plan was not approved at this time.
Grading Plan comments:
1. The proposed stabilization of Northmanor Wash at the location where the concrete pipe is to be removed does not meet the requirements of the rezoning conditions. Revise the proposed wash treatment to minimize the hardscaping while providing the necessary grade control. David Kay of Standard Pacific Homes proposed some possible solutions in our meeting on Friday, May 6.
Revise the Grading Plan to address all of these comments and resubmit three copies of the Grading plan . If you would like to meet with me to discuss any of these comments please call me at (520) 791-5550 ext. 1161 or email me at loren.makus@tucsonaz.gov.

Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services


May 12, 2005

Revisions to the grading plan were presented by MMLA on May 11.
Based on discussions with Manny Padilla and Albert Elias of Urban Planning and Design, I determined that the revisions presented by MMLA are acceptable under the rezoning conditions.
Loren Makus
05/14/2005 DAVID RIVERA ZONING REVIEW Approved
05/17/2005 ANDREW CONNOR NPPO REVIEW Approv-Cond

Final Status

Task End Date Reviewer's Name Type of Review Description
05/19/2005 ANGIE SHOFFSTALL APPROVAL SHELF Completed
05/19/2005 DHERRON1 OUT TO CUSTOMER Completed