Permit Number: T04PL01814
Parcel: 111063930

Address:
2862 N EDITH BL

Review Status: Completed

Review Details: PLUMBING

Permit Number - T04PL01814
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/23/2005 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide plumbing plans to a known scale. Reference Section 103.2.3, UPC 1994.
2. Revise the drawing to clearly show the location of the dryer and the furnace. Reference Section 103.2.3, UPC 1994.
3. Size natural gas pipe using Table 12-3, UPC 1994 or provide calculations demonstrating conformance to Section 1217.3, UPC 1994. Correct the total for the connected gas load to agree with the individual gas loads.
4. Provide a shut off valve and indicate the BTUH gas load at each service location.
5. Show the location and size of the water meter on the plans. Reference Section 103.2.3, UPC 1994.
6. Revise the drawing to clearly show the location of the water service entrance and shut off valve along with their relationship to the water piping in the building. Label the sizes of all of the pipe sections. Reference Section 103.2.3, UPC 1994.
7. Provide water pressure and pipe sizing calculations per Sections 610.1 and 610.4 of the 1994 UPC and in accordance with the PEX manufacturer's installation instructions. The water pressure range for the address can be obtained from Tucson Water at 791-2631.
8. Show how the HW and CW are to be installed between the two buildings.
9. Provide combustion air for the water heater and show the flue (size, height, and termination).
10. Clarify the routing of the building drains, show the size of each pipe section, and the size of each trap.
11. Clarify the relationship between the two building sewers. Show all of the cleanouts from the point of connection to the building drain to the HCS at the public sewer.
12. Show the grade of the 4" building sewer.
13. If the plumber reroutes any plumbing lines (Note #2), a revision to the project will be required.

Final Status

Task End Date Reviewer's Name Type of Review Description
02/23/2005 BETH GRANT OUT TO CUSTOMER Completed