Permit Number: T04PL01443
Parcel: Unknown

Address:
10249 E RITA RD

Review Status: Completed

Review Details: PLUMBING

Permit Number - T04PL01443
Review Name: PLUMBING
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/12/2004 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Indicate which buildings will require backwater valves. Reference Section 710.1, UPC 1994.
2. Revise the size of the RPBP's as required to comply with Section 610.2, UPC 1994.
08/18/2004 TACHONG1 WWM REVIEW Needs Review