Permit Review Detail
Review Status: Completed
Review Details: PLUMBING
Permit Number - T04PL00360
Review Name: PLUMBING
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/14/2004 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Further review of the submitted pedicure units and discussions with the manufacturer of the unit has resulted in the following change in requirements: 1. Reduced pressure backflow preventers are required for both hot water and cold water connections. 2. Each unit shall be provided with separate backflow devices. |