Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04OT02551
Parcel: 110121020

Address:
2715 N WYATT DR

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T04OT02551
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2005 PAUL MACHADO ENGINEERING REVIEW Denied To: Mark P. McCarty, P. E. DATE: January 31, 2005
McCarty Engineering, Inc.
1745 E. River Road, Suite 101
Tucson, Arizona 85718
SUBJECT: Hospice Facility at TMC, 2715 N. Wyatt Drive
Grading Plan T04BU03082 (First Review)
Floodplain Use Permit T04OT02551 (First Review)
T13S, R14E, Section 35

RESUBMITTAL REQUIRED: Grading Plan, Drainage Report, Floodplain Use Permit and SWPPP

The Grading Plan (GP) and Drainage Report (DR), Floodplain Use Permit (FUP) and SWPPP cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Grading Plan:

1. Please include a response letter to the comments along with the corrected copies of the GP.
2. Grade basin to drain.
3. Call out the quantity and interval of concrete drainage blocks for the screen walls.
4. Curb returns and wheelchair ramps will be required at both ingress/egress locations with 18' min. radii.
5. Call out the maintenance access ramp for the retention basin. The width for the ramp is 15' min. and the slope is 8:1 min.
6. Show the 100-year flood peak discharge.
7. Slopes of 3H: 1V require hand placed riprap.
8. Slopes of 2H: 1V or greater require grouted riprap.
9. Cut or fill slopes require a 2' minimum setback from property line.
10. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. Please address.

Drainage report:

1. Please include a response letter to the comments along with the corrected copies of the DR.
2. The conversion from NVGD 29 to NAVD 88 to establish the Lowest Floor Elevation does not include Chapter 26.5.2 requirement of 12" above the base flood elevation. Revise as necessary.
3. According to paragraph 2 in Chapter 2 "Project Description", the DR of Wyatt Street improvements was used for reference for this project. Add a statement in this DR that you have reviewed the data from the DR from the Wyatt Street improvements and agree to that data. The same statement to that effect shall be added to this DR for the Wyatt Street improvement plans phase II.
4. Complete the last sentence in the last paragragh in Chap. 4 "Floodplain and Erosion Hazard Management" to read that the project site will not be subject to erosion from the Acadia Wash. Otherwise without the addition of the "Arcadia Wash" in the sentence, the sentence implies the project may not affected by any other erosion on the property.
5. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. The suggested min. LFE form the DR is: COT datum = FEMA +2.45', 2449.0 + 2.45' = 2451.45' BFE, BFE + 12" = 2452.45 LFE. Is this correct? Revise DR as necessary.
6. An elevation certificate will need to be completed when the building has been constructed and returned to the engineering division for COT records dept. prior to the issuance of a C of O.
7. Percolation tests are required prior to the issuance of a grading permit.

Floodplain Use Permit:
1. Placement of fill in excess of 2' above existing grade at any location in the outer 100' of the developing site is not allowed and/or shall meet the requirements per D.S. 11-01. The suggested min. LFE form the DR is: COT datum = FEMA +2.45', 2449.0 + 2.45' = 2451.45' BFE, BFE + 12" = 2452.45 LFE. Is this correct? Revise DR as necessary.
2. The FUP cannot be approved prior to the grading plan approval.

Stormwater pollution prevention plan:
1. The SWPPP has been denied until the grading plan can be revised and at that time engineering will accept the SWPPP.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
C:/2715 N. Wyatt Dr. Grad

Final Status

Task End Date Reviewer's Name Type of Review Description
04/14/2005 BETH GRANT OUT TO CUSTOMER Completed
04/14/2005 ANGIE SHOFFSTALL REJECT SHELF Completed