Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04OT02520
Parcel: 11517037A

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T04OT02520
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/31/2005 DOUG WILLIAMS ENGINEERING REVIEW Denied SUBJECT: Drainage Statement/Floodplain Use Permit review
DATE: 31 January 2005
ACTIVITY NUMBERS: T04CM05068/T04OT025250
T14S, R13E, Section 3

Engineering Division has reviewed the Subject items, and approval is not recommended at this time. Please provide a Hydrology Report addressing the comments provided below at a minimum, and include a response letter addressing all comments.

**In accordance with Tucson Code, Section 26-11.2 (i), a review fee of $150.00 will be required prior to resubmittal**

Drainage Statement/Floodplain Use Permit:

Refer to Development Standard (DS) 10-02.0 (City of Tucson's Standards Manual for Drainage Design and Floodplain Management), Section 2.3, 5.2 and Tucson Code, Sections 26-5.2 and 26-11-Floodway Fringe and Floodplain permitting requirements, respectively.

1. Include the name, address and telephone number of the project owner and client for whom the report was prepared, if different (DS 10-02.0, Sec. 2.3.1.1 B, C).
2. Provide a table of contents - numbered sequentially, with reference to any appendices (DS 10-02.0, Sec. 2.3.1.1 G
3. The report must address the size, location and hydrologic characteristics of the upstream watershed which affects the site, in accordance with DS 10-02.0, Section 2.3.1.3 A 2).
4. Specify elevation data in the report exhibit for flood depths and the proposed structure's floor elevation to be in accordance with Federal Emergency Management (FEMA) floodplain development requirements. Elevation data must be in accordance with National Geodetic Vertical Datum (NGVD) 1929 for FEMA floodplain development and permitting requirements. Provide North American Vertical Datum (NAVD) 1988 - or a conversion for such from NGVD 29 - as will be necessary for site/grading plan approval. The site plan must include a local benchmark elevation with reference to City datum (NAVD 1988), and reference City Field Book and Page or GPS control point - this information may be available at: http://tdotmaps.transview.org/mapguide_mwf_tdot.htm (DS 2-02.2.1 A 23).
5. Depict 100-year floodplain limits and areas of sheet flooding resulting from 100-year flood peaks of 100-cfs or greater on a site plan contained within the report (El Rio Wash - a federally mapped floodplain). Include spot- or water surface elevations, ground contours, and clearly label the regulatory floodplain as such on the site, grading or drainage plan (DS 10-02 - Sections 2.3.1.4 C 1- 6 & Sec. 5.2.1, 5.2.4 & 5.2.5).
6. Provide an encroachment analysis demonstrating no adverse impact will occur to adjacent properties - upstream or downstream or in the public right of way, and that there will not be an increase in the Base Flood Elevation by more than .1' (Tucson Code, Section 26-.5.2).
7. The report must provide erosion protection and lowest floor elevation recommendations based upon El Rio Wash 100-year flooding depths and velocities (Tucson Code, Sec. 26-5.2
SITE PLAN:
1. Depict 100-year floodplain limits and water surface elevations onsite (DS 2-02.2.1 A 15).
2. Depict drainage patterns, proposed finish floor elevation and finish grades (DS2-02.2.1 A 16)
3. Provide estimated cut and fill quantities DS 2-02.2.1 A 17).
4. Depict existing topographic contours and provide a benchmark based on City of Tucson Datum, including city field book and page number (DS 2-02.2.1 A 23).
5. Demonstrate water harvesting maximization onsite, in accordance with the City of Tucson's Land Use Code (LUC) Section 3.7.1.
6. Depict and label a concrete Driveway apron at the property entrance, to be constructed per Pima County/City of Tucson Standard Detail 206.
7. Depict, label and dimension new 5' sidewalk, 2' from back of curb, to be constructed in the Riverview Bl. right-of-way (DS 3-01.3.3 A, B)

Resubmittal will require a complete hydrology report and a revised site plan addressing all items listed above. Subsequent comments may be necessary upon resubmittal depending on the nature and extent of revisions that occur to the report and/or exhibits.
In accordance with Tucson Code, Section 26-11.2 (i), a review fee of $150.00 will be required prior to resubmittal.
If you have any questions, I can be reached at 791-5550, extension 1189 or Doug.williams@tucsonaz.gov

Douglas Williams
Sr. Engineering Associate
Engineering Division
Development Services Department

Final Status

Task End Date Reviewer's Name Type of Review Description
02/10/2005 TAMI ACHONG OUT TO CUSTOMER Completed
02/10/2005 ANGIE SHOFFSTALL REJECT SHELF Completed