Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04OT02482
Parcel: 11304275D

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T04OT02482
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/28/2004 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: December 28, 2004
ACTIVITY NUMBER: T04OT02482/T04CM05483/T04CM05484
PROJECT NAME: Elzey Residence
PROJECT ADDRESS: 1009 & 1013 East Halcyon
PROJECT REVIEWER: Patricia Gilbert

FLOODPLAIN USE PERMIT IS DENIED

RESUBMITTAL REQUIRED: SITE PLAN, DRAINAGE REPORT, FLOODPLAIN USE PERMIT APPLICATION

1. Specify on the site/plot plan the datum and the water surface elevation (WSE) in the hydrology report. Please note the datum used for the WSE and the Finish Floor Elevation (FFE) must match or a conversion needs to take place.

2. Label the FFE on the site plan that is given in the hydrology report.

3. Change each plan to reflect the correct address.

4. Include a note on the site plan that the site is in a FEMA Special Flood Hazard Zone AE. DS 2-02.2.1.A.15.

5. Please note a condition of this permit contains a requirement that the applicant, or the applicant's authorized representative, complete a FEMA Elevation Certificate and is returned to DSD Engineering prior to approval of special inspection.

Final Status

Task End Date Reviewer's Name Type of Review Description
12/28/2004 SUE REEVES OUT TO CUSTOMER Completed
12/28/2004 SUE REEVES REJECT SHELF Completed