Permit Number: T04OT02448
Parcel: 112032240

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T04OT02448
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/06/2005 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: January 6, 2005
ACTIVITY NUMBER: T04OT02448/T04CM04213
PROJECT NAME: Guest House to 2524 East Kleindale Road
PROJECT ADDRESS: 2524 East Kleindale Road
PROJECT REVIEWER: Patricia Gilbert

FLOODPLAIN USE PERMIT IS DENIED

RESUBMITTAL REQUIRED: SITE PLAN, FLOODPLAIN USE PERMIT APPLICATION

1. Please include Water Surface Elevation (WSE) on the Site Plan. The WSE for this site is 2386.35'.

2. Add a general note to the site plan stating the entire property is in FEMA Flood Hazard AE.

3. Because the WSE for the site is 2386.35', the finish floor elevation (FFE) must be one foot above the WSE. The proposed FFE for the guest house is 2385.11', this is too low. Revise the FFE to be one foot above the WSE. Chapter 26-5.2.9.

4. Please note a condition of this permit contains a requirement that the applicant, or the applicant's authorized representative, complete a FEMA Elevation Certificate and is returned to DSD Engineering prior to approval of special inspection.

Final Status

Task End Date Reviewer's Name Type of Review Description
01/21/2005 TAMI ACHONG OUT TO CUSTOMER Completed
01/21/2005 TAMI ACHONG REJECT SHELF Completed