Permit Number: T04OT01761
Parcel: 12112022C

Review Status: Completed

Review Details: SITE

Permit Number - T04OT01761
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/07/2004 JIM EGAN FIRE REVIEW Denied 1. Remove center island from circular drive or provide circular drive with a minimum 36' inside radius and a 53'-6" outside radius.
2. Provide detail for gate entry indicating a minimum 20 feet wide opening width for gate(s) and location for emergency fire apparatus ingress device (lock box).
09/09/2004 BLANCA ESPINO ENGINEERING REVIEW Denied Site Plan
1. Please include a response letter with the next submittal that states how all comments have been addressed. Include plans/redlines from previous plan submittal.

2. The 5 foot pedestrian access aisle is to be called out as a sidewalk as per D.S.2-08.4.1.A. Sidewalks cannot be flushed with asphalt. D.S. 2-08.4.0 Drainage flowing across all pedestrian circulation paths shall be conveyed under the path for up to ten (10) year frequency flood events. D.S. 2-08.3.1

3. Sidewalks or pedestrian refuge areas may not be located between any motor vehicle parking space and the PAAL providing access to that space. Relocate pathway between handicap parking area. D.S. 2-08.4.E

4. Show adjacent driveways. Closed unused driveways/curb cuts. A permit will be required from Permits and Codes for any work in the right-of-way. Contact Permits & Codes on the 3rd floor of the Public Works building, City side. D.S. 2-02.2.1.A.18

5. Demonstrate refuse vehicle maneuverability fully dimensioned around Center of Transformer area. Refuse vehicles require 36' inside radius and 50' outside radius.

6. Graphically identify detail 3, Drive Section with a symbol as redlined on Sheet 0.1

7. Full code compliance required.
09/13/2004 Andrew Connor LANDSCAPE REVIEW Needs Review
09/15/2004 TACHONG1 HANDICAP-SITE REVIEW Needs Review
09/15/2004 TACHONG1 ZONING REVIEW Needs Review
09/15/2004 TACHONG1 NPPO REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
09/15/2004 TAMI ACHONG OUT TO CUSTOMER Completed