Permit Number: T04OT01737
Parcel: 138170370

Address:
475 E ELVADO RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T04OT01737
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/19/2005 LOREN MAKUS ENGINEERING REVIEW Denied DATE: January 27, 2005
TO: Steve Whillier, Conestoga-Rovers and Associates
SUBJECT: Site Plan: TIAA Superfund Site
REVIEWER: Loren Makus
ACTIVITY NUMBER: T04CM03976, T04BU02516 and T04OT01737

SUMMARY: The Site Plan and Grading Plan were reviewed by Development Services Department, Engineering Division on September 22, 2004. This review is only for the project parcels along Elvado Road, outside of the Tucson International Airport. The portion of the project within the Airport was reviewed for floodplain issues only. The Site Plan and Grading Plan were not approved for the Elvado Road parcels. Please address the following comments.


1. Clearly show the existing and proposed drainage patterns on the Elvado parcels. The TIA master drainage report and the City of Tucson TSMS study indicate that there is a significant discharge through the culverts under Nogales Highway. Label the discharge quantity on the site/grading plan. Discuss the disposition of the discharge in a drainage statement or drainage report.
2. Determine the 100-year water surface elevation and the extent of the City of Tucson floodplain for the discharge. Provide the supporting calculations in the drainage statement/report.
3. Provide details showing transition from the fill area to natural grade. Show that the toes of all fill slopes will be set back at least two feet from the property line.
Revise the Site Plan, to address all of these comments and resubmit two copies of each for review. Include a letter explaining how each comment has been addressed.
Loren Makus, E.I.T.
Senior Engineering Associate
Engineering Division
Development Services

Final Status

Task End Date Reviewer's Name Type of Review Description
03/16/2005 BETH GRANT OUT TO CUSTOMER Completed
03/16/2005 ANGIE SHOFFSTALL REJECT SHELF Completed