Review Date Reviewer's Name Type of Review Description Status Comments
08/11/2004 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: August 11, 2004
ACTIVITY NUMBER: T04OT01578
PROJECT NAME: Carport for 2541 East Kleindale
PROJECT ADDRESS: 2541 East Kleindale
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN


1. The finish floor elevation must be on the site/plot plan for the proposed carport. The water surface elevation for the area in question is 2386.60'. The finish floor elevation must be on e foot above the water surface elevation. Revise the plan to show the finish floor elevation.

2. Please see attached documents; elevation certification form and instructions. The elevation Certificate is required and must be returned to Development Services prior to final inspection. If you have any questions please contact me at 791-5550.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/17/2004 LISA LESNY OUT TO CUSTOMER Completed
08/17/2004 SUE REEVES REJECT SHELF Completed