Permit Number: T04OT01418
Parcel: 12604012B

Address:
4414 E 2ND ST

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T04OT01418
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/16/2004 PATRICIA GILBERT ENGINEERING REVIEW Denied DATE: July 16th, 2004
ACTIVITY NUMBER: T04OT01418
PROJECT NAME: B' nai B'rith Covenant House of Tucson
PROJECT ADDRESS: 4414 East 2nd Street
PROJECT REVIEWER: Patricia Gilbert

The following items must be revised or added to the site plan. Please include a response letter with the next submittal that states how all comments have been addressed.

RESUBMITTAL REQUIRED: SITE PLAN, FLOODPALIN USE APPLICATION


1. It is acknowledged that on sheet A-5 there is a note stating the proposed addition will be built a the same elevation as the existing structure. However for plan clarity include this statement on sheet A-1 in location near the proposed addition.

2. Once the addition is constructed an elevation certificate will have to be completed by a registered land surveyor and returned to the Development Services Department prior to Final Inspection of the completed addition. For your convenience I have attached a blank elevation certificate.

3. I have also enclosed the completed elevation certificate for the structure. The elevation certificate that was submitted was not complete. For an elevation certificate to be complete, a licensed registered land surveyor is required to seal (stamp) the document.