Permit Number: T04OT01317
Parcel: 122050600

Address:
4342 E EDISON ST

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T04OT01317
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
09/01/2004 JIM TATE ENGINEERING REVIEW Denied DATE: September 1, 2004
ACTIVITY NUMBER: T04CM02380
PROJECT ADDRESS: 4342 E. Edison
PROJECT REVIEWER: James C. Tate, P.E., CFM

Flood Use Permit is denied.

Resubmittal Required: Site Plan, Flood Use Permit Application

GENERAL COMMENTS:

1. A Flood Use Permit is required prior to Site Plan approval. PRIOR REVIEW COMMENT

1. Sheet 3 Note 7 of the Site Plan specifies the FFE as 12 inches above existing grade. This is incorrect. The Hydrology Statement specifies the FFE as at or above 2459.1 ft. NGVD-29. Remove Note 7. PRIOR REVIEW COMMENT

2. It appears that the intent is to elevate the building on stem walls. However, the plan is not clear. Elevation on fill requires the building to be set back 25 ft. from the fill line unless a registered professional engineer recommends a closer distance and it is approved by the city. Elevation on fill also requires bank protection to safeguard against flood incurred erosion. Again, in the absence of a grading plan, it can not be determined how the building is proposed to be elevated.