Permit Review Detail
Review Status: Completed
Review Details: FLOODPLAIN
Permit Number - T04OT01317
Review Name: FLOODPLAIN
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/12/2004 | JIM TATE | ENGINEERING | REVIEW | Denied | DATE: July 12, 2004 ACTIVITY NUMBER: TOTCM01317 PROJECT ADDRESS: 4342 E. Edison PROJECT REVIEWER: James C. Tate, P.E., CFM Flood Use Permit is denied. Resubmittal Required: Site Plan GENERAL COMMENTS: 1. This Flood Use Permit is required prior to Site Plan approval. 2. The Finish Floor Elevation (FFE) shown on the plans is incorrect. The Hydrology Report specifies that the FFE must be one foot above the 100-yr. peak water surface elevation. The Site Plan shows the FFE as one foot above existing grade. The Hydrology Report specifically calls out the FFE required for building 1 as 2459.1 NGVD-29. All appropriate sheets of the plan must specify this elevation and datum. An Elevation Certificate filled out by a registered land surveyor will be required to be returned to Development Services prior to final inspection of the structure. The FFE must be at or above 2459.1 NGVD-29 or final inspection will not be granted. All mechanical equipment (i.e. air conditioning compressors, hot water heaters, furnaces, etc) must also be placed at or above 2459.1 NGVD-29. This will also be shown on the Elevation Certificate. Correct the plans to show the proper FFE. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/31/2004 | DELMA ROBEY | OUT TO CUSTOMER | Completed |