Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T04OT01317
Parcel: 122050600

Address:
4342 E EDISON ST

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T04OT01317
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/12/2004 JIM TATE ENGINEERING REVIEW Denied DATE: July 12, 2004
ACTIVITY NUMBER: TOTCM01317
PROJECT ADDRESS: 4342 E. Edison
PROJECT REVIEWER: James C. Tate, P.E., CFM

Flood Use Permit is denied.

Resubmittal Required: Site Plan

GENERAL COMMENTS:

1. This Flood Use Permit is required prior to Site Plan approval.

2. The Finish Floor Elevation (FFE) shown on the plans is incorrect. The Hydrology Report specifies that the FFE must be one foot above the 100-yr. peak water surface elevation. The Site Plan shows the FFE as one foot above existing grade. The Hydrology Report specifically calls out the FFE required for building 1 as 2459.1 NGVD-29. All appropriate sheets of the plan must specify this elevation and datum. An Elevation Certificate filled out by a registered land surveyor will be required to be returned to Development Services prior to final inspection of the structure. The FFE must be at or above 2459.1 NGVD-29 or final inspection will not be granted. All mechanical equipment (i.e. air conditioning compressors, hot water heaters, furnaces, etc) must also be placed at or above 2459.1 NGVD-29. This will also be shown on the Elevation Certificate. Correct the plans to show the proper FFE.

Final Status

Task End Date Reviewer's Name Type of Review Description
08/31/2004 DELMA ROBEY OUT TO CUSTOMER Completed