Permit Number: T04OT01147
Parcel: 11205035D

Address:
3109 N OLSEN AV

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T04OT01147
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2004 JIM TATE ENGINEERING REVIEW Denied DATE: June 17, 2004
ACTIVITY NUMBER: T04OT01147
PROJECT NAME: Olsen Condominiums
PROJECT ADDRESS: 3109 N. Olsen Ave.
PROJECT REVIEWER: James C. Tate, P.E., CFM

Resubmittal Required: Flood Use Permit Application, Grading Plan

The following items must be corrected.

1. A copy of the stamped approved Tentative Plat must be included with the Grading Plan submittal.

2. A Flood Use Permit is required prior to Grading Plan approval.

3. Structures located in a floodplain must be elevated one foot above the 100-yr. peak WSEL. The floodplain ordinance (Tucson Code Chapter 26) defines structures as anything with walls and/or a roof. The attached garages are structures and must be elevated. The plan shows the FFE of these garages to be less than one ft. above the base flood. Re-design and properly elevate the garages.

4. Please note that all machinery and/or equipment (furnaces, hot water heaters, heat pumps, air conditioners, etc) must be elevated one foot above the base flood. Tucson Code Chapter 26 Section 5.2

5. In floodplain areas where fill is to be used to raise the elevation of a building site, the building line must be located not less than twenty-five feet land ward from any edge of the fill, unless a study prepared by a registered professional civil engineer shows a lesser distance is acceptable. Tucson Code Chapter 26, Sec 8(d)