Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T04OT01040
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/23/2005 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | DATE: June 29, 2005 TO: Richard Reigle, Reigle & Associates SUBJECT: Safeway Store 1684, Site Plan Review and Floodplain Use Permit Application Review REVIEWER: Loren Makus ACTIVITY NUMBER: T04OT01039 and T04OT01040 SUMMARY: The Site Plan and Floodplain Use Permit were reviewed by Development Services Department, Engineering Division on June 28, 2004. The Site Plan and Floodplain Use Permit were not approved at this time. Please address the following comments. Site Plan Comments: 1. Provide the basis for bearing (Development Standard (DS) 2-02.2.1.A.5)) The basis of bearing is required on the site plan as the site plan is used as a reference for any future development. The basis of bearing may be presented graphically. Since the basis of bearing on the grading plan is described as the west line of section 17, this may be labelled on the site plan as the basis of bearing. Include two found monuments on the line with complete descriptions. 2. The minimum font size for all lettering on the plan must be 12 point. This is for legibility when the plans are microfilmed. Revise the plan accordingly. 3. Revise note 17 to require the use of truncated domes on existing access ramps within the project boundary. Drainage Report Comments 4. The Drainage Report is accepted for site plan review purposes. Floodplain Use Permit Application 5. The Floodplain Use Permit will be issued in conjunction with the Grading Permit. Revise the Site Plan to address these comments and resubmit two copies for review. Include a letter explaining how each comment has been addressed. Loren Makus, E.I.T. Senior Engineering Associate Engineering Division Development Services |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 08/09/2005 | JMORALE1 | OUT TO CUSTOMER | Completed |
| 08/09/2005 | SUE REEVES | REJECT SHELF | Completed |