Permit Number: T04OT00771
Parcel: 137051270

Address:
4920 S 12TH AV

Review Status: Completed

Review Details: RESUBMITTAL - SITE ALL

Permit Number - T04OT00771
Review Name: RESUBMITTAL - SITE ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
07/09/2004 Jim Egan FIRE REVIEW Approved
07/12/2004 Andrew Connor NPPO REVIEW Passed
07/12/2004 Andrew Connor LANDSCAPE REVIEW Denied 1) Add notes to site plan: Landscape Buffer 5' wide / Max 30" high / Predominantly Landscaped and Oleander hedge 5' / 36" on center per approved site plan dated 1/21/1986
07/28/2004 Doug Williams ENGINEERING REVIEW Denied SUBJECT: 4620 S. 12th Ave.
REVIEWER: Doug Williams
DATE: 28 JULY 2004
ACTIVITY NUMBERS: T04OT00771

SUMMARY: Engineering Division has reviewed the Site Plan received on 7 July 2004. Approval is not recommended at this time. Please address the following comments:

1. Provide a location map (Development Standard - DS - 2-02.2.1.4).
2. Indicate on the plan whether the manufactured office is existing or proposed. Label the size height, overhangs and any canopies (DS 2-02.2.1.6).
3. Depict existing and future sight visibility triangles for a driveway intersecting an arterial roadway. The future curb location is typically 11' from the future right of way line for 100' MS&R rights of way. Please note that the future half right-of-way width is 65' for 12th Avenue, extending southward 300' from the intersection centerlines of 12th Avenue and Irvington Road. See "redlines" on plan (DS 2-02.2.1 A 10 & 3-01.5.0).
4. Dimension the ingress/egress width, if to be used. Closure of all unused curb cuts will be required (DS 2-02.2.1.11).
5. Depict drainage patterns, proposed finished floor elevation(s) and finish grades (DS 2-02.2.1.16).
6. Depict the Major Streets and Routes (MS&R) half, or full right of way. Assure intersection widening requirements are included in the depiction/delineation (DS 2-02.2.1.19).
7. Revise the typical landscape buffer detail to omit any required landscaping from the public right of way, unless already existing - identify as such, if existing (DS 2-02.2.1.27).
8. Depict the existing refuse provision/container location, size and access thereto fully dimensioned and labeled, if onsite. If existing pickup is curbside, indicate such on the plan (DS 2-02.2.1 A32 & DS 6-01.0).

* A right of way permit will be required for any work in the public right of way. Contact Permits and Codes - Tucson Department of Transportation (TDOT) at 791-5100 for questions.
If you have any questions, I can be reached at 791-5550, extension 1189 or Dwillia1@ci.tucson.az.us.

Doug Williams
Sr. Engineering Associate
Engineering Division
Development Services Department
08/11/2004 Peter McLaughlin ZONING REVIEW Denied SITE PLAN TRANSMITTAL

TO: Mike Spiess FROM: Peter McLaughlin
4920 S. 12th Ave Senior Planner
Tucson, AZ 85706
(520) 889-8989

FOR: Patricia Gehlen
Principal Planner
Development Services Dept.

PROJECT:
T04OT00771
Used Car Lot for
Southwest Cars & Trucks
4920 S. 12th Avenue
Site Plan Review (1st review)

TRANSMITTAL: August 12, 2004


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Per IBC Sec. 1106.4, the one handicapped parking space provided must be van accessible, and be provided with an access aisle with a minimum width of 8 feet. Please revise drawing and detail, which show only a 5-foot aisle. Also, there must be accessibility between the new h/c parking space and the building and street frontages. Provide the maximum slope of the handicapped ramp and access aisles to be provided.
ANS/ IBC

2. Add the development designator under the zoning information. The development designator for the vehicle sales use in the C-2 zone is "31". Also add the restrictions which the proposed use is subject to. The vehicle sales use in the C-2 zone is subject to LUC 3.5.9.5.A and 3.5.9.5.B., which limit the use of outdoor lighting. If any new freestanding lighting is proposed, detail on the drawing to demonstrate compliance.
DS 2-02.2.1.A.31
LUC 2.5.4.2.B.6

3. Revise parking calulation to be based on one vehicle space per 250 square feet of office GFA plus 1 vehicle space per 10,000 square feet of gross lot area. LUC 3.3.4

4. Add the existing and future sight visibility triangles at the access drive and at the intersection of 12th Ave and Nevada Street DS 2-02.1.A.10

5. Add a Floor Area Ratio calculation to the site plan including maximum allowed and proposed FAR. The FAR is calculated as the Gross Floor Area divided by the site area. The maximum allowed FAR per development designator 31 is 0.90. DS 2-02.2.2.A.3
LUC 3.2.11

6. Dimension clearly all MS&R street monument lines from 12th Ave. centerline, including future curbs, and future right-of-way, and future sidewalks.
DS 2-02.2.1.A.19 and .21

7. Dimension building setbacks to the north and south property lines. Also, dimension the MS&R setback from back of future curb along 12th Avenue.
DS 2-02.2.1.A.7
LUC 3.2.6.4
LUC 3.2.6.5

8. Provide the height and dimensions of the proposed building on the site plan. DS 2-02.2.1.A.6

9. Dimension wheelstop curb from the front of parking space at 2- ½ feet. DS 2-02.2.1.13

10. Provide a copy of the permit / approved site plan for the modular building previously removed from this property and placed on property to the west.

11. Provide a location map in the upper right hand corner of the plan. DS 2-02.2.1.A.4


If you have any questions about this transmittal, please call Peter McLaughlin, (520) 791-5608.


PMc\siteplans03\T03OT00771a
08/12/2004 PETER MCLAUGHLIN HANDICAP-SITE REVIEW Denied See zoning review comments.

Final Status

Task End Date Reviewer's Name Type of Review Description
09/20/2004 TAMI ACHONG OUT TO CUSTOMER Completed
09/20/2004 ANGIE SHOFFSTALL REJECT SHELF Completed