Permit Number: T04OT00751
Parcel: 11101035B

Address:
3800 E RIVER RD

Review Status: Completed

Review Details: SITE

Permit Number - T04OT00751
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2004 MICHAEL ST. PAUL HANDICAP-SITE REVIEW Approved
04/12/2004 JIM EGAN FIRE REVIEW Approved
05/04/2004 Joseph Linville NPPO REVIEW Approved Exception per 2002 PC aerial photo.
05/04/2004 PAUL MACHADO ENGINEERING REVIEW Denied To: Phred Bartholomaei DATE: April 30, 2004
Architect
3800 E. River Road
Tucson, Arizona 85719

SUBJECT: 3800 E. River Road
Site plan T04OT00751 (First Review)
Floodplain Use Permit T04OT00752
T13S, R14E, Section 28

RESUBMITTAL REQUIRED: Site Plan , Hydrology Report and Floodplain Use Permit


The Site Plan (SP), Hydrology Report (HR) and Floodplain Use Permit (FUP) cannot be approved as submitted. Please address the following review comments prior to the next submittal.


Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. A grading plan may be required.
3. The Floodplain Use Permit will be issued upon the acceptance of the HR.
4. All walls, including retaining walls and benches that retain soil will require a separate permit and submittal.
5. Please provide property description per D.S. 2-02.2.1.3.
6. Show the limits of the 100-year floodplain and water surface elevation per D.S. 2-02.2.1.15.
7. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
8. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
9. Please provide existing topographic contours at intervals not exceeding two (2) feet and/or spot elevations as pertinent and Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
10. Show Site plan number on all sheets per D.S. 2-02.2.1.29.
11. List the consulting engineer and the owner/developer on the plans with the pertinent information.
12. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
13. Show how equipment area/enclosure will drain.



Hydrology Report:
1. Please include a response letter to the comments along with the corrected copies of the HR.
2. The Floodplain Use Permit will be issued upon the acceptance of the HR.
3. A Hydrology report is required for parcels affected by 100 year flows of 100 cfs, of more per S.M.D.D.F.M., chap. II, 2.1.2.
4. The content and format of the Hydrology report should follow S.M.D.D.F.M., chap. II, 2.1.3.
5. Place all service facilities such as electrical and heating equipment at or above the regulatory flood elevation per Chap. 26 -5.1.11 of the floodplain and erosion hazard management code.
6. Show how equipment area/enclosure will drain.
7. Show the project address on the cover of the Hydrology report.


If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax

Final Status

Task End Date Reviewer's Name Type of Review Description
05/07/2004 LISA LESNY OUT TO CUSTOMER Completed
05/04/2004 ANGIE SHOFFSTALL REJECT SHELF Completed