04/12/2004 JIM EGAN FIRE REVIEW Approved
04/27/2004 DAN CASTRO HANDICAP-SITE REVIEW Denied Detail disabled parking and access aisles. Dimension same. Post disabled parking signs. (2002 IBC) (ICC/ANSI-A117.1-1998)
04/27/2004 Daniel Castro ZONING REVIEW Denied COMMENTS: Please attach a response letter with the next
Submittal, which states how all Zoning Review Section comments Regarding the Land Use Code and Development Standards were Addressed.
CODE SECTION/ DEVELOPMENT STANDARD

1. Provide documentation for access rights onto private road from new access located in south west corner of the site. If easement is provided, list the recording information (docket/page) on the plan. If written agreement, please provide a copy of the agreement for City records. (D.S. 2-02.2.1.A.11)

2. Revise the MS&R perimeter yard setbacks noted listed under project data 4c. MS&R setback is based on the greater of: 21 feet or the building height measured from the back of future curb. (LUC Sec. 3.2.6.5.B.1) (D.S. 2-02.2.1.A.7)

3. Detail disabled parking and access aisles. Dimension same. Post disabled parking signs. (2002 IBC) (ICC/ANSI-A117.1-1998)

4. Review of this plan by the Zoning Review Section may be done over the counter. Please contact Dan Castro to set an appointment.

If you have any questions about this transmittal, please call Dan Castro, (520) 791-5608.
04/29/2004 PAUL MACHADO ENGINEERING REVIEW Denied To: Artie Vigil DATE: April 29, 2004
Ellermann and Schick Architects
727 E. Maryland Ave.
Phoenix, Arizona 85014

SUBJECT: 6230 E. Broadway Blvd.
Site plan T04OT00747 (First Review)
T14S, R14E, Section 13

RESUBMITTAL REQUIRED: Site Plan and Drainage Statement.

The Site Plan (SP) and Drainage Statement (DS) cannot be approved as submitted. Please address the following review comments prior to the next submittal.

Site Plan:

1. Please include a response letter to the comments along with the corrected copies of the SP.
2. Label existing and future sight visibility triangles per D.S. 2-02.2.1.10.
3. Fully dimensioned loading space(s) and maneuvering area(s) per D.S. 2-02.2.1.14. Also see note no. 16.
4. Please provide Drainage patterns and finished grades per D.S. 2-02.2.1.16.
5. Please list estimated cut & fill quantities per D.S. 2-02.2.1.17.
6. All easement of record must be graphically shown on the plan together with recording docket and page per D.S. 2-02.2.1.20.
7. Dimension from street monument lines to existing and proposed curbs, sidewalks, driveways, and utility lines per D.S. 2-02.2.1.21.
8. Please provide a Bench Mark based on City of Tucson Datum, including City Field Book and page number per D.S. 2-02.2.1.23.
9. Show Site plan number on all sheets per D.S. 2-02.2.1.29.
10. Show refuse container location, size, and access thereto fully dimensioned per D.S. 2-02.2.1.32 and D.S. 6-01.0.The proposed refuse enclosure locations do not meet COT standards. Approval from Environmental Services is required for the present locations. Contact John Clark at 791-5543.
11. A permit or a private improvement agreement will be necessary for any work performed within the Right-of-way. Contact Permits and Codes at (520) 791-5100 for permit information.
12. Please show a typical cross section of the P.A.A.L. or call out the percentage of slopes. Call out the GB at the D/W, if applicable.
13. Please show the proposed roof drainage patterns, 100% of the 10-year flow must be conveyed under the sidewalks including any other site drainage as well. Please provide supporting calculations to demonstrate compliance with D.S. 3-01.4.4. If the location(s) of the roof scuppers have not yet been decided, a general note indicating sidewalk scuppers will be used when the roof scuppers locations have been designed and located will suffice.
14. Add note: "Depress all landscaped areas 6" maximum for water harvesting".
15. Please list area of disturbance. Please show on the site plan areas that will require new asphalt and/or areas that will require removal and/or replacement of asphalt. A Stormwater pollution prevention plan (SWPPP) may be required. Contact Paul P. Machado at 791-5550 x1193.

Drainage Statement:
1. A Drainage Statement is required. A DS is a brief description of drainage conditions applicable for a site which is not affected be 100-year flows of 100 cfs, or more, and is neither subject to detention requirements nor impacted by flows from a significant watercourse per S.M.D.D.F.M., chap. II, 2.1.3.
2. The content and format of the DS should follow S.M.D.D.F.M., chap. II, 2.1.3.
3. Show the project address on the cover of the Drainage Statement.

If you have any questions, I can be reached at 791-5550 x1193 or Paul.Machado@tucsonaz.gov
Paul P. Machado
Senior Engineering Associate
City of Tucson/Development Services Department
201 N. Stone Avenue
P.O. Box 27210
Tucson, Arizona 85726-7210
(520) 791-5550 x1193 office
(520) 879-8010 fax
04/30/2004 Andrew Connor NPPO REVIEW Denied Submit NPPO plan or Application for Exception per
DS 2-15.0
04/30/2004 Andrew Connor LANDSCAPE REVIEW Denied 1) Indicate on landscape plan existing and future sight visibility triangles per DS 2-02.2.1.10

2) Revise General Note on sheet L2 as necessary. All new development is required to meet LUC provisions per LUC 3.7.1.2.A. Development. Any human alteration to the state of land, including its vegetation, soil, geology, or hydrology, for any residential, commercial, industrial, utility.
LUC Sec. 6.2.4 Definitions http://www.ci.tucson.az.us/planning/luc/art6div2.pdf

3) Show existing and augmented vegetation on sheet L3 in Wilmot Rd street landscape border per DS 2-07.2.2.A.1.e

4) Street landscape borders shall be located entirely on site, except that, if approved by the City Engineer or designee per LUC 3.7.2.4.A.2.

5) Landscape plan shall include irrigation specification design and layout per DS 2-07.5.4.A & DS 2-07.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation.

6) Submit NPPO plan or Application for Exception per
DS 2-15.0

Final Status

Task End Date Reviewer's Name Type of Review Description
05/03/2004 TAMI ACHONG OUT TO CUSTOMER Completed
05/03/2004 SUE REEVES REJECT SHELF Completed