Permit Number: T04OT00738
Parcel: 132092430

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T04OT00738
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/10/2004 LOREN MAKUS ENGINEERING REVIEW Denied The Floodplain Use Permit T04OT00738 cannot be approved at this time. Under the Floodplain Ordinance, (Tucson Code Chapter 26-4.1) any structure that is substantially repaired or improved at a value equal or greater than 50 percent of the value of the structure must fully comply with all requirements of the Chapter. The value of the previous fire repair (T00CM03555) and the value of the proposed improvements exceed the limit. For a Floodplain Use Permit to be approved the following conditions must be met:
1. Provide a qualified appraisal of the value of the main house separate from the property and the other structures, and
2. Limit the scope of the proposed improvements so that the total value of the proposed improvements and of the previously completed repairs and improvements do not exceed 50 percent of the value of the structure, or
3. Elevate the floor of the proposed improved area above the level of the regulatory flood elevation and not change the openings between the existing interior space and the proposed improvements.

If you have any questions or want to set up a meeting please call me at 520.791.5550 x 1161 or e-mail me at loren.makus@tucsonaz.gov.

Loren Makus, E.I.T.
Senior Engineering Associate

Final Status

Task End Date Reviewer's Name Type of Review Description
05/11/2004 LISA LESNY OUT TO CUSTOMER Completed
05/10/2004 ANGIE SHOFFSTALL REJECT SHELF Completed