Permit Number: T04OT00708
Parcel: 112050530

Review Status: Completed

Review Details: FLOODPLAIN

Permit Number - T04OT00708
Review Name: FLOODPLAIN
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
04/06/2004 BLANCA ESPINO ENGINEERING REVIEW Denied 1. Add note to General Notes: All roof spouts will be routed under any adjacent sidewalk. Sidewalks shall be flood free for all storm discharges of up to a 10-year flood event.

2. General Notes #18 is incorrect. The project site is in a FEMA Floodplain, Zone AE as per Panel 1639K, dated February 8, 1999. Correct and revise.

3. Justify the FFE for proposed structure. My calculations for the BFE is 2385.75, therefore the FFE is 2386.75.

Final Status

Task End Date Reviewer's Name Type of Review Description
04/29/2004 TAMI ACHONG OUT TO CUSTOMER Completed
04/29/2004 ANGIE SHOFFSTALL REJECT SHELF Completed