Permit Number: T04OT00523
Parcel: 117142310

Address:
626 S 6TH AV

Review Status: Completed

Review Details: SITE

Permit Number - T04OT00523
Review Name: SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
03/16/2004 JIM EGAN FIRE REVIEW Approved
03/16/2004 Blanca Espino ENGINEERING REVIEW Denied Site Plan
1. Indicate property description. D.S. 2-02.2.1.A.2

2. Indicate correct project address. D.S. 2-02.2.1.A.3

3. Indicate existing and future sight visibility triangles. SVT's for P.A.A.L. to Arterial are Near 345', Far 125'. D.S. 2-02.2.1.A.10

4. If applicable, indicate location, type, size and height of existing and proposed signage. D.S. 2-02.2.1.A.13

5. Do not obstruct offsite to onsite flows. Drainage design around Back-up Spur is unacceptable. Correct and revise. D.S. 2-02.2.1.A.16

6. Indicate if street is Public or Private. Indicate adjacent driveways. D.S. 2-02.2.1.A.18

7. Dimensioned right-of-way, including any applicable Major Streets and Routes (MS&R) Plan right-of-way. D.S. 2-02.2.1.A.19

8. All curb cuts, curb returns and curb depressions should be located in accordance with the City of Tucson Code, Chapter 25. The minimum curb return radius for an arterial street to a P.A.A.L. is 25-feet. TAMG 5.5

9. A back-up spur will be provided at the end of a row of parking if no ingress or egress is provided at the end. The spur will be a minimum of three (3) feet in depth, will have a three (3) foot radii, and will have a wheel barrier to prevent encroachment onto any unsurfaced areas. Aminimum distance of three (3) feet will be provided between the back of spur and any wall, screen, or other obstruction over six (6) inches in height. When the last space in a bay of parking is wider than eight and one-half (8 ½ ) feet, the back-up spur can be reduced in size, subject to approval by the Traffic Engineer. D.S. 3-05.2.2.D & 6.0.Figure 2
04/08/2004 Andrew Connor NPPO REVIEW Denied Submit NPPO plan or Application for Exception per
DS 2-15.0
04/08/2004 Andrew Connor LANDSCAPE REVIEW Denied 1) Include legal description and correct address of site per DS 2-07.2.1.B.1

2) One canopy tree must be provided for every thirty-three (33) linear feet of landscape border. 1 additional tree is required in the north landscape buffer along 6th. Ave per LUC 3.7.2.4

2) Trees that are located in areas of required landscaping will be a minimum fifteen (15) gallon container size per
DS 2-06.3.5.C

3) Fifty % or more of the street landscape border area must have shrubs and vegetative ground cover.
DS 2-06.3.5.A

4) 20% of shrubs in landscape border are required to be 5 gallon size DS 2-06.3.5.F

5) Indicate both the proper and common name of each type of plant material DS 2-07.2.2.A.d

6) Screens may be located in the landscape border if the criteria indicated in LUC3.7.3.2 are met. The existing walls along 6th Ave do not comply

7) Indicate type of screening material for new 5' screen wall. All walls are required to be of masonry material or masonry with stucco or textured finish. LUC 3.7.3.7.A.1


8) Landscape plan shall include irrigation specification design and layout per DS 2-07.5.4.A & DS 2-07.5.4.B including source of irrigation, sleeves for driveways and sidewalks, locations of valves, low-flow bubblers or drip irrigation.


9) The landscape plan shall indicate use of all runoff, from individual catch basins around single trees to basins accepting flow from an entire vehicular use area or roof area.
LUC 3.7.4.3.B

10) Provide screening for refuse container(s) per LUC Table 3.7.2-I

11) A 6' screen for refuse storage is required for 6th Ave. and all adjacent properties LUC 3.7.2-I

12) Submit NPPO plan or Application for Exception per
DS 2-15.0
04/10/2004 PATRICIA GEHLEN HANDICAP-SITE REVIEW Denied See Zoning comments
04/10/2004 PATRICIA GEHLEN ZONING REVIEW Denied CITY OF TUCSON DEVELOPMENT SERVICES DEPARTMENT
ZONING REVIEW SECTION

DATE: April 10, 2004
ACTIVITY NUMBER: T04OT00523
PROJECT NAME: Restrip and pave parking lot
PROJECT ADDRESS: 626 South 6th Ave
PROJECT REVIEWER: Patricia Gehlen

The following items must be revised on or added to the site plan. Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed:

1) Add legal descriptions and addresses to site plan (DS 2-02.2.1.A.2 & 3),
2) Location map should be revised to eliminate a reference to Blacklidge Drive (DS 2-02.2.1.A.4),
3) Please add the GFA of the building to the Land Use Code Data (DS 2-02.2.2.B.2),
4) Dimension the width of the proposed parking spaces and the distance of the wheel stops from the front of the parking spaces (DS 2-01.2.2.A.8, 3-05.2.3.C.2),
5) Detail handi-cap access from the parking spaces to the sidewalk (ramps and slopes as required) and detail the proposed signage,
6) If the bicycle parking is proposed, please fully dimension location on the site plan. If it is existing, please identify the existing location (DS 2-02.2.1.A.9, DS 2-09),
7) The general notes indicate a loading zone is provided yet it could not be located. Revise the site plan as required (DS 2-02.2.1.A.14).

Final Status

Task End Date Reviewer's Name Type of Review Description
04/19/2004 CINDY AGUILAR OUT TO CUSTOMER Completed
04/12/2004 SUE REEVES REJECT SHELF Completed