Permit Number: T04OT00076
Parcel: 13014019K

Address:
4602 E 29TH ST

Review Status: Completed

Review Details: RESUBMITTAL - SITE

Permit Number - T04OT00076
Review Name: RESUBMITTAL - SITE
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
05/11/2004 David Rivera ZONING REVIEW Denied DSC TRANSMITTAL

FROM: David Rivera
Senior Planner

FOR: Patricia Gehlen
Principal Planner

PROJECT: T04OT00076
El Sur Auto Sales
4602 E. 29th St.
Site Plan

Transmittal date: 2nd Review May 11, 2004

COMMENTS: Please resubmit revised drawings along with redlines and a response letter, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.

1. Now that the number of required parking spaces and location have been established the following items must be addressed. A back-up spur is required at the end of a row of parking spaces. The back-up spur must be located at least three feet from the edge of the sidewalk. The back-up spur can be wheel stops or extruded curbing and must be the full length of a 24-foot PAAL. See redlines. Also per your response comments the display area was depicted but the display area is not depicted on the plan. The display area or limits thereof must be shown dimensioned or indicated by display parking spaces and must not interfere with vehicular use area for the required parking. Also clarify if the area to the south od the building is to be used for display or something else.

(Portion of the Previous Comment: The vehicle parking area has not been dimensioned correctly or defined. PAAL areas must be labeled and dimensioned, wheel stops must be provided in front of the vehicle parking spaces, the vehicle display must be defined, dimensioned and labeled. Some form of barrier, wheel stops, extruded curbing, will be required if front of the display parking areas in order to keep vehicles from overhanging onto the landscape border or to keep vehicles from damaging any required screening at the back of the border. The barrier must be placed at least two and one-feet from the front of the parking space. Label the type of proposed barrier and dimension as required. Label the pavement type and thickness.) See D.S. 3-05 for more information regarding vehicular use area design. DS 2-02.2.1.A.8

2. The PAAL areas for the required vehicular use areas or parking areas have not been defined or dimensioned on the plan. (Previous Comment: Define, dimension, and label on the plan the PAAL area. DS 2-02.2.1.A.11)

3. I do not believe that the sight visibility triangles have been correctly drawn on the plan. The future curb and sidewalk locations have not been drawn, labeled or dimensioned per the MSR&R cross section for a 120-foot right-of-way. The future curb location is 9 feet from the future right-of-way line. (Previous Comment: Indicate on the plan the location, type and size of existing or proposed freestanding signage or existing billboards. DS 2-02.2.1.A.13)

4. This comment was not addressed. (Previous Comment: 29th Street is listed as a major street on the Major Street and Routes Map and is subject to future right-of-way and roadway widening. Please show existing and future curb and sidewalk locations based on the existing and future right-of-way widths. See additional Engineering comments. DS 2-02.2.1.A.19)

5. This comment was not completely addressed. (Previous Comment: List as a note the existing and proposed uses. The proposed use must be listed as follows, "Vehicle Rental and Sales Use" DD 31 Subject To LUC sections 3.5.9.5.A. and .B.)


If you have any questions about this transmittal, please call David Rivera, (520) 791-5608.





RESUBMITTAL OF THE FOLLOWING IS REQUIRED: Revised site plan and landscape plan and requested documents.
05/12/2004 DAVID RIVERA HANDICAP-SITE REVIEW Approved
05/19/2004 Andrew Connor LANDSCAPE REVIEW Denied 1) Areas where plants are susceptible to injury by vehicular or pedestrian traffic must be protected by appropriate means, such as curbs, bollards, wheel stops, or low walls per LUC 3.7.2.3.B Provide protection from the VUA for landscape border along 29th St.

2) A 6' wall is required for refuse storage per LUC Table 3.7.2-I. Revise Dumpster enclosure `detail as necessary.

3) The landscape plan shall indicate use of all runoff, from individual catch basins around single trees to basins accepting flow from an entire vehicular use area or roof area.
LUC 3.7.4.3.B. Include note on plan: Landscape border shall be depressed for water harvesting

4) Identify entire paved area on plan, including fully dimensioned layout per DS 2-02.2.1.A.8
06/03/2004 Loren Makus ENGINEERING REVIEW Denied June 3, 2004
To: Luis Omar Mejia
RE: Site Plan Review for El Sur Auto Sales T04OT00076
Reviewer: Loren Makus

The site plan was reviewed by the Engineering Division of Development Services on June 3, 2004. The site plan was not approved at this time. Please revise the site plan in accordance with the following comments.

1. The current Major Streets and Routes map indicates that 29th Street is an arterial with a future width of 100 feet. Revise the future curb location, future right-of-way line and the existing and future site visibility triangles to be consistent with this.
2. Show roof drainage patterns. Show that pedestrian areas will be flood free for all discharges up to a 10-year event.
3. Show locations of driveways on adjacent properties. Adjacent driveways should be 80 feet apart with no more than 2 driveways within 300 feet

Submit a revised site plan meeting all of the requirements of the development standards. Include a letter describing how each of these comments has been addressed. If you have any questions or if you wish to set up a meeting, call me at 791-5550 ext. 1161 or email me at loren.makus@tucsonaz.gov.

Loren Makus, E.I.T.
Senior Engineering Associate

Final Status

Task End Date Reviewer's Name Type of Review Description
06/04/2004 EGRANT1 OUT TO CUSTOMER Completed
06/04/2004 ANGIE SHOFFSTALL REJECT SHELF Completed