Permit Number: T04EL02418
Parcel: 126134840

Address:
1134 S SWAN RD

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL02418
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/09/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04EL02418 DENIED 12/09/04

1. Since the N-G bond takes place in the service disconnects, the grounds in the feeders between the CT can and disconnects consist of a redundant path to ground. Please remove.
2. Feeders on load side of service disconnects need OCPDs.
3. If the OCPD in the 400A disconnect is rated 400A, the ground needs to be a minimum of #3, not #4.
4. Question the practice of two disconnects feeding one gutter. Willing to discuss.