Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL02277
Review Name: ELECTRICAL
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/29/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04EL02277 DENIED 11/16/04 1. Provide electrical site drawing with location of all equipment. 2. Apply project address to plans. 3. Indicate nature of existing service. Only if such service is overhead may we permit overhead upgrade. 4. Provide TEP available fault current. 5. Specify fault current rating of equipment. 6. Indicate voltage and phase on line diagram. |