Permit Number: T04EL02277
Parcel: 124050460

Address:
805 E 4TH ST #01

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL02277
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04EL02277 DENIED 11/16/04
1. Provide electrical site drawing with location of all equipment.
2. Apply project address to plans.
3. Indicate nature of existing service. Only if such service is overhead may we permit overhead upgrade.
4. Provide TEP available fault current.
5. Specify fault current rating of equipment.
6. Indicate voltage and phase on line diagram.