Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL02261
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 12/06/2004 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Approved | T04EL02261 DENIED 12/03/04 1. Minimum font size is 10 point, which is a little over 1/8". 2. Put all four different street addresses on their appropriate meters. 3. New AC needs addition of Mechanical plans to project. 4. Please correct 30% demand factor for load calculations, or justify otherwise. 5. Specify there the #4 CU GND is to be bonded to. |