Permit Review Detail
Review Status: Completed
Review Details: ELECTRICAL
Permit Number - T04EL02206
Review Name: ELECTRICAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/07/2005 | LINDA BUCZYNSKI | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T04EL02206 DENIED 010705 1. Show location of new fused disconnect on plans. 2. Plans shall be executed in sufficient detail to emable Plans Examiner to determine compliance with NEC 110.26 clearance requirements. 3. Show load on new panel. No electrical loads are shown on this project. This being the case, we would not permit the new panel. 4. The #6 in the conduit between the new transformer and disconnect, sized per NEC Table 250.66, shall be a #4. 5. Calculations total 400A, not 300A. And 80% is not a methodology to calculate load. 6. Clarify intent of box marked KW KWH. 7. It is not clear from the plans what the intent is. What is existing metering configuration, what is new. Please clarfiy, and coordinate proper addressing among Pima County, city DSD, and plans. 8. Need 2 sets of plans for over-the-counter approvals. |