Review Details: ELECTRICAL

Permit Number - T04EL01986
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/10/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04CM01986 DENIED 12/06/04
1. Relocation of meter would also involve relocation of certain related equipment, such as service disconnect, grounding electrode system, and extension of conductors. This should be diagrammed on plans. See the attached sheet for Electrical Permitting Requirements. Indicate voltage and phase, size of service entrance conductors, size and specification of grounding electrode system, rating of all overcurrent protective devices, relocation of feeder for sign.