Permit Number: T04EL01707
Parcel: 122140110

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL01707
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04EL01707 DENIED 8/17/04

1. Revise the plans to add a requirement to Provide placards at both service disconnects, denoting the presence of the other. NEC 230.2 (E).
2. Per David Mann, there needs to be a fire wall between a laundry and dwelling. Identify such adjacent walls as firewalls on plans. A Building Inspector will be sent to verify. Take out a building permit for such verification, linked to this permit.