Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T04EL01706
Parcel: 122140110

Review Status: Completed

Review Details: ELECTRICAL

Permit Number - T04EL01706
Review Name: ELECTRICAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/19/2004 LINDA BUCZYNSKI ELECTRICAL-COMMERCIAL REVIEW Approved T04EL01706 DENIED 8/17/04

1. Revise the plans to add a requirement to Provide placards at both service disconnects, denoting the presence of the other. NEC 230.2 (E).
2. Per David Mann, there needs to be a fire wall between a laundry and dwelling. Identify such adjacent walls as firewalls on plans. A Building Inspector will be sent to verify.
Take out a building permit for such verification, linked to this permit.